Pioneering the future of power testing and monitoring

SF6 quality

Gas-Insulated Substation (GIS) and Circuit Breaker Monitoring SF6 quality and leaks

GIS PD and SF6 monitoring tells the story inside out.
See the sparks before they strike — with PD monitoring in your GIS and SF₆ tracking at your side, reliability isn’t a guess, it’s a guarantee.

Circuit Breaker Monitoring & Optimizing system

Know your breakers before they fail. Power View Circuit Breaker Monitoring & Optimizing system records every trip and close coil current signature and compares it to a learned baseline, turning subtle waveform changes into clear early warnings. It tracks key features—inrush peak, buffer-valley current/time, saturation time, and discharge duration—to expose latch friction, auxiliary switch delays, and coil or mechanical degradation long before an outage. User-set thresholds trigger alarms for true anomalies, enabling condition-based maintenance that can defer or eliminate offline tests. Built-in compliance support simplifies NERC PRC-005 verification by proving trip-coil operability from online records. A compact hub with clip-on sensors and secure COMTRADE/CSV export (SFTP) streamlines analysis and reporting, while real-time notifications keep crews ahead of issues. Ultra-long-range communication helps monitor assets spread across plants or remote sites without new cabling.